-It can be designed according to the desired power and energy options in power electronic devices.
-It can be designed in different ways for ups, inverter, modular structure.
-For Ups, this panel includes UPS-31 and similar devices.
-Powered by User-Friendly HMI options.
-It can be adapted to the desired device dimensions in panels in accordance with IP standards.
Input Characteristics | |
Rectifier | 02/06/12-pulse SCR rectifier or IGBT Switched PWM rectifier |
Rated input voltage | 380/400/415VAC, 4-wire (A, B, C, PE) |
Rated operating frequency | 50Hz/60Hz |
Input voltage range | -15%~+10% |
Input frequency range | -5%~+5% |
Input power factor | up to 0.90 (SCR) up to 0.99 (IGBT) |
DC Characteristics | |
Blocking Diode (Optional) | Inside UPS Cubicle |
DC switch | Inside UPS Cubicle |
Nominal voltage | 110/125/144/220/360VDC (or customizable voltage level) |
Battery type | Lead acid, nickel cadmium |
Inverter output voltage | Single-phase 110/220VAC (5-60kVA) / three-phase 380/400/415VAC (10-100kVA) |
Output power factor | 0.8 |
Voltage stability (Steady state) | <± 1% |
Voltage stability (Transient) | (0-100%) <±10% |
Transient response time | (20-150) ms |
Inverter overload capacity | 110%: 10 minutes, 125%: 2 minutes, 150%: 10 seconds |
THDv (100% linear load) | 3% |
THDv (100% non-linear load) | 8% |
Efficiency | up to 90% (depends on power rating) |
Bypass | |
Bypass input voltage | Single-phase 110/220VAC/ three-phase 380/400/415VAC |
Bypass voltage range | -10%~+ 10% |
Maintenance bypass switch | Make before break maintenance switch |
Static Switch | |
Frequency | 50Hz/60Hz |
Frequency synchronization | ± 5% Hz |
Overload capacity | 300% 100ms |
System | |
Noise | 53~70dB |
Ingress Protection | IP20 up to IP42 |
Color | RAL7035 (other colors according to customer requirements) |
Cable entry | Bottom (top cable entry as option) |
HMI | It can be download from webpage |
Communication interface | MODBUS RTU RS485 (SNMP, IEC61850, MODBUS TCP option) |
Free contacts | Programmable 8 dry contacts from HMI |
Operating Environment | |
Operating temperature | Range 0 to 50 °C (constant operation at full load at 40 °C) |
Relative humidity | 0 to 95% without condensation |
Altitude | ≤ 1000m; above 1000m, load is derated by 1% for every increase of 100m |